SS 8: Lifts and escalators

Last reviewed 30 October 2026 · Sources: MBIE, NZ legislation and council guidance

SS 8 covers lifts, escalators, travelators and other systems that move people or goods within buildings: passenger lifts (8/1), platform, low-speed and service lifts (8/2), and escalators and moving walks (8/3). MBIE's handbook sets out annual IQP inspections against standards such as NZS 4332 and EN 115-1.

At a glance

Specified systemSS 8
Official nameLifts, escalators, travelators, or other systems for moving people or goods within buildings
Sub-categoriesSS 8/1 Passenger-carrying lifts
SS 8/2 Platform, low-speed and service lifts
SS 8/3 Escalators and moving walks
Typical intervalsAnnual (varies by task; see below)
Standards often citedNZS 4332, EN 81-20, EN 81, NZS 4334, EN 115-1
Annual certificateForm 12A from an IQP, attached to the building warrant of fitness

What SS 8 covers

  • Passenger-carrying lifts must be listed in all cases; examples a high-speed office elevator and a platform lift for disabled access.[1]
  • 8/2 covers platform and low-speed lifts (typically low-rise, 0.3 m/s or less) other than in a single household unit, and service lifts such as dumb waiters, book hoists, vehicle stacking systems and stage lifts.[1]
  • 8/3 examples: a mall escalator and a horizontal moving walkway; must be listed in all cases.[1]
  • Lifts need building consent and a code compliance certificate; the compliance schedule then sets ongoing maintenance and inspection carried out by IQPs.[2]
  • A household unit with a cable car needs a compliance schedule for the cable car only.[1]

How often it is inspected

SystemDailyWeeklyMonthly3-monthly6-monthlyAnnual2–5 yr
SS 8 Lifts and escalatorsnononononono
Typical inspection, testing and maintenance intervals mentioned in MBIE and council guidance. A dot means the interval appears for at least part of the system, by the owner or an IQP.
TaskTypical frequencyWho
8/1 annual checklist (Handbook pp 30-32) / NZS 4332 or EN 81 testsAnnualIQP[3]
Test interface with building emergency warning system, if connectedAnnual—[1]
8/2 inspection to NZS 4334 Appendix A / checklist pp 34-35AnnualIQP[3]
8/3 inspection to EN 115-1 / checklist p 37AnnualIQP[3]
Keep IQP reports2 yearsOwner[2]

What an inspection typically covers

  • 8/1 machine room: supports, door security, lighting, ventilation, circuit diagrams, hand-winding equipment.[1]
  • 8/1 machinery: sheaves, brake operation and linings, governor.[1]
  • 8/1 lift well and pit: hoisting ropes and terminations, guide rails, buffers, pit safety switch.[1]
  • 8/1 car: safety gear, door protective devices, rating plate, alarms and emergency telephone, emergency trapdoor.[1]
  • 8/1 landing doors: locks, emergency opening, door operation.[1]
  • 8/1 hydraulic lifts: hoses, ram, cylinder, flow restriction valve, manual lowering, anti-creep device.[1]
  • 8/1 operation: safety switches, emergency lighting, fire-condition operation, load weighing device.[1]
  • 8/1 accessibility: floor levelling, door dwell time, landing indicators, handrails.[1]
  • 8/1 general: incorrect repairs or modifications; maintenance records kept.[1]
  • 8/2: machinery space, brake, drive belts, safety gear, landing door interlocks, slack-rope and emergency switches.[1]
  • 8/3: stop switches, overspeed protection, brakes, steps/pallets, comb plates, balustrades and skirting, handrails.[1]

Standards commonly cited

StandardTitle
NZS 4332:1997Non-domestic passenger and goods lifts (as modified by D2/AS1); Part 4 Tests for inspection[3]
EN 81-20:2014Safety rules for lifts for transport of persons and goods (as modified by D2/AS1); Annex C.1[3]
EN 81 Part 1 or 2, Annex D clause D.2Annual tests plus Handbook checklist pp 30-32 for EN 81 lifts[1]
Power Lift RulesRules in force at installation, for lifts installed before the Building Act 1991[1]
NZS 4334:2012 Appendix APlatform lifts and low-speed lifts; Appendix A Inspection and routine maintenance[3]
Rules for Power Lifts Not Exceeding 750 Watts (1 H.P.)For 8/2 installations predating D2/AS2[1]
EN 115-1:2008 clause 7.4Safety of escalators and moving walks (as modified by D2/AS3)[1]

Titles as listed in council and MBIE documents. Inspections follow the standard and edition named in the building's compliance schedule, usually the edition the system was installed to. Changing to a different edition needs an amendment to the compliance schedule.

Building Code context

  • Consent requires showing the lift meets NZBC Clause D2 Mechanical installations for access, via D2 Acceptable Solution or an alternative solution.[2]
  • Handbook cites D2/AS1 (lifts, NZS 4332 / EN 81), D2/AS2 (platform and low-speed lifts, NZS 4334), D2/AS3 (escalators and moving walks, EN 115).[1]

Questions

How often is SS 8 inspected?

MBIE and council guidance shows tasks at these intervals: annual, with an IQP certifying the system each year. The building's compliance schedule sets the actual frequency.

Which standards apply to SS 8?

Commonly cited: NZS 4332, EN 81-20, EN 81, NZS 4334, EN 115-1. The compliance schedule names the standard and edition for each building.

Who can certify SS 8?

An independently qualified person (IQP) registered with the council for this system. They issue a Form 12A each year, which the owner attaches to the building warrant of fitness.

Sources

  1. Compliance Schedule Handbook, Amendment 3 — MBIE, 14 February 2014 (first published 25 May 2007)
  2. Lifts and Building Act requirements — MBIE, 2006-08-01 (confirmed current Feb 2016)
  3. Specified Systems Guidance for Customers, WBCA 003 v1.0.1 — Westland District Council BCA, 16 September 2025

General information only, not legal or engineering advice. Last reviewed 30 October 2026. Spotted something out of date? Let us know.

certify.nz includes a starting checklist for SS 8. Edit it to match the building's compliance schedule, inspect offline and issue a signed report.

Start free for 30 days